GenericDER
PowerSystems.GenericDER — Typemutable struct GenericDER <: DynamicInjection
name::String
Qref_Flag::Int
PQ_Flag::Int
Gen_Flag::Int
PerOp_Flag::Int
Recon_Flag::Int
Trv::Float64
VV_pnts::NamedTuple{(:V1, :V2, :V3, :V4), Tuple{Float64, Float64, Float64, Float64}}
Q_lim::MinMax
Tp::Float64
e_lim::MinMax
Kpq::Float64
Kiq::Float64
Iqr_lim::MinMax
I_max::Float64
Tg::Float64
kWh_Cap::Float64
SOC_ini::Float64
SOC_lim::MinMax
Trf::Float64
fdbd_pnts::NamedTuple{(:fdbd1, :fdbd2), Tuple{Float64, Float64}}
D_dn::Float64
D_up::Float64
fe_lim::MinMax
Kpp::Float64
Kip::Float64
P_lim::MinMax
dP_lim::MinMax
T_pord::Float64
rrpwr::Float64
VRT_pnts::NamedTuple{(:vrt1, :vrt2, :vrt3, :vrt4, :vrt5), Tuple{Float64, Float64, Float64, Float64, Float64}}
TVRT_pnts::NamedTuple{(:tvrt1, :tvrt2, :tvrt3), Tuple{Float64, Float64, Float64}}
tV_delay::Float64
VES_lim::MinMax
FRT_pnts::NamedTuple{(:frt1, :frt2, :frt3, :frt4), Tuple{Float64, Float64, Float64, Float64}}
TFRT_pnts::NamedTuple{(:tfrt1, :tfrt2), Tuple{Float64, Float64}}
tF_delay::Float64
FES_lim::MinMax
Pfa_ref::Float64
Q_ref::Float64
P_ref::Float64
base_power::Float64
states::Vector{Symbol}
n_states::Int
ext::Dict{String, Any}
internal::InfrastructureSystemsInternal
endParameters of a Generic Distributed Energy Resource Model. Based on "Modeling Framework and Coordination of DER and Flexible Loads for Ancillary Service Provision."
Arguments
name::String: Name of the component. Components of the same type (e.g.,PowerLoad) must have unique names, but components of different types (e.g.,PowerLoadandACBus) can have the same nameQref_Flag::Int: Reactive Power Control Mode. 1 VoltVar Control, 2 Constant Q Control, 3 Constant PF Control, validation range:(1, 3)PQ_Flag::Int: Active and reactive power priority mode. 0 for Q priority, 1 for P priority, validation range:(0, 1)Gen_Flag::Int: Define generator or storage system. 0 unit is a storage device, 1 unit is a generator, validation range:(0, 1)PerOp_Flag::Int: Defines operation of permisible region in VRT characteristic. 0 for cease, 1 for continuous operation, validation range:(0, 1)Recon_Flag::Int: Defines if DER can reconnect after voltage ride-through disconnection, validation range:(0, 1)Trv::Float64: Voltage measurement transducer's time constant, in s, validation range:(0, nothing)VV_pnts::NamedTuple{(:V1, :V2, :V3, :V4), Tuple{Float64, Float64, Float64, Float64}}: Y-axis Volt-var curve points (V1,V2,V3,V4)Q_lim::MinMax: Reactive power limits in pu (Qmin, Qmax)Tp::Float64: Power measurement transducer's time constant, in s, validation range:(0, nothing)e_lim::MinMax: Error limit in PI controller for q control (emin, emax)Kpq::Float64: PI controller proportional gain for q control, validation range:(0, nothing)Kiq::Float64: PI controller integral gain for q control, validation range:(0, nothing)Iqr_lim::MinMax: Limit on rate of change for reactive current (pu/s) (Iqrmin, Iqrmax)I_max::Float64: Max. inverter's current, validation range:(0, nothing)Tg::Float64: Current control's time constant, in s, validation range:(0, nothing)kWh_Cap::Float64: BESS capacity in kWh, validation range:(0, nothing)SOC_ini::Float64: Initial state of charge (SOC) in pu, validation range:(0, 1)SOC_lim::MinMax: Battery's SOC limits (SOCmin, SOCmax)Trf::Float64: Time constant to estimate system frequency, in s, validation range:(0, nothing)fdbd_pnts::NamedTuple{(:fdbd1, :fdbd2), Tuple{Float64, Float64}}: Frequency error dead band thresholds(fdbd1, fdbd2)D_dn::Float64: reciprocal of droop for over-frequency conditions, in pu, validation range:(0, nothing)D_up::Float64: reciprocal of droop for under-frequency conditions, in pu, validation range:(0, nothing)fe_lim::MinMax: Frequency error limits in pu (femin, femax)Kpp::Float64: PI controller proportional gain for p control, validation range:(0, nothing)Kip::Float64: PI controller integral gain for p control, validation range:(0, nothing)P_lim::MinMax: Active power limits in pu (Pmin, Pmax)dP_lim::MinMax: Ramp rate limits for active power in pu/s (dPmin, dPmax)T_pord::Float64: Power filter time constant in s, validation range:(0, nothing)rrpwr::Float64: Ramp rate for real power increase following a fault, in pu/s, validation range:(0, nothing)VRT_pnts::NamedTuple{(:vrt1, :vrt2, :vrt3, :vrt4, :vrt5), Tuple{Float64, Float64, Float64, Float64, Float64}}: Voltage ride through v points (vrt1,vrt2,vrt3,vrt4,vrt5)TVRT_pnts::NamedTuple{(:tvrt1, :tvrt2, :tvrt3), Tuple{Float64, Float64, Float64}}: Voltage ride through time points (tvrt1,tvrt2,tvrt3)tV_delay::Float64: Time delay for reconnection after voltage ride-through disconnection, validation range:(0, nothing)VES_lim::MinMax: Min and max voltage for entering service (VESmin,VESmax)FRT_pnts::NamedTuple{(:frt1, :frt2, :frt3, :frt4), Tuple{Float64, Float64, Float64, Float64}}: Frequency ride through v points (frt1,frt2,frt3,frt4)TFRT_pnts::NamedTuple{(:tfrt1, :tfrt2), Tuple{Float64, Float64}}: Frequency ride through time points (tfrt1,tfrt2)tF_delay::Float64: Time delay for reconnection after frequency ride-through disconnection, validation range:(0, nothing)FES_lim::MinMax: Min and max frequency for entering service (FESmin,FESmax)Pfa_ref::Float64: (default:0.0) Reference power factor, validation range:(0, nothing)Q_ref::Float64: (default:0.0) Reference reactive power, in pu, validation range:(0, nothing)P_ref::Float64: (default:1.0) Reference active power, in pu, validation range:(0, nothing)base_power::Float64: (default:100.0) Base power of the unit (MVA) for per unitizationstates::Vector{Symbol}: (Do not modify.) The states of GenericDER depend on the Flagsn_states::Int: (Do not modify.) The states of GenericDER depend on the Flagsext::Dict{String, Any}: (default:Dict{String, Any}()) An extra dictionary for users to add metadata that are not used in simulation.internal::InfrastructureSystemsInternal: (Do not modify.) PowerSystems.jl internal reference
InfrastructureSystems.get_name — Methodget_name(value::GenericDER) -> String
Get GenericDER name.
PowerSystems.get_D_dn — Methodget_D_dn(value::GenericDER) -> Float64
Get GenericDER D_dn.
PowerSystems.get_D_up — Methodget_D_up(value::GenericDER) -> Float64
Get GenericDER D_up.
PowerSystems.get_FES_lim — Methodget_FES_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER FES_lim.
PowerSystems.get_FRT_pnts — Methodget_FRT_pnts(
value::GenericDER
) -> @NamedTuple{frt1::Float64, frt2::Float64, frt3::Float64, frt4::Float64}
Get GenericDER FRT_pnts.
PowerSystems.get_Gen_Flag — Methodget_Gen_Flag(value::GenericDER) -> Int64
Get GenericDER Gen_Flag.
PowerSystems.get_I_max — Methodget_I_max(value::GenericDER) -> Float64
Get GenericDER I_max.
PowerSystems.get_Iqr_lim — Methodget_Iqr_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER Iqr_lim.
PowerSystems.get_Kip — Methodget_Kip(value::GenericDER) -> Float64
Get GenericDER Kip.
PowerSystems.get_Kiq — Methodget_Kiq(value::GenericDER) -> Float64
Get GenericDER Kiq.
PowerSystems.get_Kpp — Methodget_Kpp(value::GenericDER) -> Float64
Get GenericDER Kpp.
PowerSystems.get_Kpq — Methodget_Kpq(value::GenericDER) -> Float64
Get GenericDER Kpq.
PowerSystems.get_PQ_Flag — Methodget_PQ_Flag(value::GenericDER) -> Int64
Get GenericDER PQ_Flag.
PowerSystems.get_P_lim — Methodget_P_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER P_lim.
PowerSystems.get_P_ref — Methodget_P_ref(value::GenericDER) -> Float64
Get GenericDER P_ref.
PowerSystems.get_PerOp_Flag — Methodget_PerOp_Flag(value::GenericDER) -> Int64
Get GenericDER PerOp_Flag.
PowerSystems.get_Pfa_ref — Methodget_Pfa_ref(value::GenericDER) -> Float64
Get GenericDER Pfa_ref.
PowerSystems.get_Q_lim — Methodget_Q_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER Q_lim.
PowerSystems.get_Q_ref — Methodget_Q_ref(value::GenericDER) -> Float64
Get GenericDER Q_ref.
PowerSystems.get_Qref_Flag — Methodget_Qref_Flag(value::GenericDER) -> Int64
Get GenericDER Qref_Flag.
PowerSystems.get_Recon_Flag — Methodget_Recon_Flag(value::GenericDER) -> Int64
Get GenericDER Recon_Flag.
PowerSystems.get_SOC_ini — Methodget_SOC_ini(value::GenericDER) -> Float64
Get GenericDER SOC_ini.
PowerSystems.get_SOC_lim — Methodget_SOC_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER SOC_lim.
PowerSystems.get_TFRT_pnts — Methodget_TFRT_pnts(
value::GenericDER
) -> @NamedTuple{tfrt1::Float64, tfrt2::Float64}
Get GenericDER TFRT_pnts.
PowerSystems.get_TVRT_pnts — Methodget_TVRT_pnts(
value::GenericDER
) -> @NamedTuple{tvrt1::Float64, tvrt2::Float64, tvrt3::Float64}
Get GenericDER TVRT_pnts.
PowerSystems.get_T_pord — Methodget_T_pord(value::GenericDER) -> Float64
Get GenericDER T_pord.
PowerSystems.get_Tg — Methodget_Tg(value::GenericDER) -> Float64
Get GenericDER Tg.
PowerSystems.get_Tp — Methodget_Tp(value::GenericDER) -> Float64
Get GenericDER Tp.
PowerSystems.get_Trf — Methodget_Trf(value::GenericDER) -> Float64
Get GenericDER Trf.
PowerSystems.get_Trv — Methodget_Trv(value::GenericDER) -> Float64
Get GenericDER Trv.
PowerSystems.get_VES_lim — Methodget_VES_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER VES_lim.
PowerSystems.get_VRT_pnts — Methodget_VRT_pnts(
value::GenericDER
) -> @NamedTuple{vrt1::Float64, vrt2::Float64, vrt3::Float64, vrt4::Float64, vrt5::Float64}
Get GenericDER VRT_pnts.
PowerSystems.get_VV_pnts — Methodget_VV_pnts(
value::GenericDER
) -> @NamedTuple{V1::Float64, V2::Float64, V3::Float64, V4::Float64}
Get GenericDER VV_pnts.
PowerSystems.get_base_power — Methodget_base_power(value::GenericDER) -> Float64
Get GenericDER base_power.
PowerSystems.get_dP_lim — Methodget_dP_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER dP_lim.
PowerSystems.get_e_lim — Methodget_e_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER e_lim.
PowerSystems.get_ext — Methodget_ext(value::GenericDER) -> Dict{String, Any}
Get GenericDER ext.
PowerSystems.get_fdbd_pnts — Methodget_fdbd_pnts(
value::GenericDER
) -> @NamedTuple{fdbd1::Float64, fdbd2::Float64}
Get GenericDER fdbd_pnts.
PowerSystems.get_fe_lim — Methodget_fe_lim(
value::GenericDER
) -> @NamedTuple{min::Float64, max::Float64}
Get GenericDER fe_lim.
PowerSystems.get_kWh_Cap — Methodget_kWh_Cap(value::GenericDER) -> Float64
Get GenericDER kWh_Cap.
PowerSystems.get_n_states — Methodget_n_states(value::GenericDER) -> Int64
Get GenericDER n_states.
PowerSystems.get_rrpwr — Methodget_rrpwr(value::GenericDER) -> Float64
Get GenericDER rrpwr.
PowerSystems.get_states — Methodget_states(value::GenericDER) -> Vector{Symbol}
Get GenericDER states.
PowerSystems.get_tF_delay — Methodget_tF_delay(value::GenericDER) -> Float64
Get GenericDER tF_delay.
PowerSystems.get_tV_delay — Methodget_tV_delay(value::GenericDER) -> Float64
Get GenericDER tV_delay.
PowerSystems.set_D_dn! — Methodset_D_dn!(value::GenericDER, val) -> Any
Set GenericDER D_dn.
PowerSystems.set_D_up! — Methodset_D_up!(value::GenericDER, val) -> Any
Set GenericDER D_up.
PowerSystems.set_FES_lim! — Methodset_FES_lim!(value::GenericDER, val) -> Any
Set GenericDER FES_lim.
PowerSystems.set_FRT_pnts! — Methodset_FRT_pnts!(value::GenericDER, val) -> Any
Set GenericDER FRT_pnts.
PowerSystems.set_Gen_Flag! — Methodset_Gen_Flag!(value::GenericDER, val) -> Any
Set GenericDER Gen_Flag.
PowerSystems.set_I_max! — Methodset_I_max!(value::GenericDER, val) -> Any
Set GenericDER I_max.
PowerSystems.set_Iqr_lim! — Methodset_Iqr_lim!(value::GenericDER, val) -> Any
Set GenericDER Iqr_lim.
PowerSystems.set_Kip! — Methodset_Kip!(value::GenericDER, val) -> Any
Set GenericDER Kip.
PowerSystems.set_Kiq! — Methodset_Kiq!(value::GenericDER, val) -> Any
Set GenericDER Kiq.
PowerSystems.set_Kpp! — Methodset_Kpp!(value::GenericDER, val) -> Any
Set GenericDER Kpp.
PowerSystems.set_Kpq! — Methodset_Kpq!(value::GenericDER, val) -> Any
Set GenericDER Kpq.
PowerSystems.set_PQ_Flag! — Methodset_PQ_Flag!(value::GenericDER, val) -> Any
Set GenericDER PQ_Flag.
PowerSystems.set_P_lim! — Methodset_P_lim!(value::GenericDER, val) -> Any
Set GenericDER P_lim.
PowerSystems.set_P_ref! — Methodset_P_ref!(value::GenericDER, val) -> Any
Set GenericDER P_ref.
PowerSystems.set_PerOp_Flag! — Methodset_PerOp_Flag!(value::GenericDER, val) -> Any
Set GenericDER PerOp_Flag.
PowerSystems.set_Pfa_ref! — Methodset_Pfa_ref!(value::GenericDER, val) -> Any
Set GenericDER Pfa_ref.
PowerSystems.set_Q_lim! — Methodset_Q_lim!(value::GenericDER, val) -> Any
Set GenericDER Q_lim.
PowerSystems.set_Q_ref! — Methodset_Q_ref!(value::GenericDER, val) -> Any
Set GenericDER Q_ref.
PowerSystems.set_Qref_Flag! — Methodset_Qref_Flag!(value::GenericDER, val) -> Any
Set GenericDER Qref_Flag.
PowerSystems.set_Recon_Flag! — Methodset_Recon_Flag!(value::GenericDER, val) -> Any
Set GenericDER Recon_Flag.
PowerSystems.set_SOC_ini! — Methodset_SOC_ini!(value::GenericDER, val) -> Any
Set GenericDER SOC_ini.
PowerSystems.set_SOC_lim! — Methodset_SOC_lim!(value::GenericDER, val) -> Any
Set GenericDER SOC_lim.
PowerSystems.set_TFRT_pnts! — Methodset_TFRT_pnts!(value::GenericDER, val) -> Any
Set GenericDER TFRT_pnts.
PowerSystems.set_TVRT_pnts! — Methodset_TVRT_pnts!(value::GenericDER, val) -> Any
Set GenericDER TVRT_pnts.
PowerSystems.set_T_pord! — Methodset_T_pord!(value::GenericDER, val) -> Any
Set GenericDER T_pord.
PowerSystems.set_Tg! — Methodset_Tg!(value::GenericDER, val) -> Any
Set GenericDER Tg.
PowerSystems.set_Tp! — Methodset_Tp!(value::GenericDER, val) -> Any
Set GenericDER Tp.
PowerSystems.set_Trf! — Methodset_Trf!(value::GenericDER, val) -> Any
Set GenericDER Trf.
PowerSystems.set_Trv! — Methodset_Trv!(value::GenericDER, val) -> Any
Set GenericDER Trv.
PowerSystems.set_VES_lim! — Methodset_VES_lim!(value::GenericDER, val) -> Any
Set GenericDER VES_lim.
PowerSystems.set_VRT_pnts! — Methodset_VRT_pnts!(value::GenericDER, val) -> Any
Set GenericDER VRT_pnts.
PowerSystems.set_VV_pnts! — Methodset_VV_pnts!(value::GenericDER, val) -> Any
Set GenericDER VV_pnts.
PowerSystems.set_base_power! — Methodset_base_power!(value::GenericDER, val) -> Any
Set GenericDER base_power.
PowerSystems.set_dP_lim! — Methodset_dP_lim!(value::GenericDER, val) -> Any
Set GenericDER dP_lim.
PowerSystems.set_e_lim! — Methodset_e_lim!(value::GenericDER, val) -> Any
Set GenericDER e_lim.
PowerSystems.set_ext! — Methodset_ext!(value::GenericDER, val) -> Any
Set GenericDER ext.
PowerSystems.set_fdbd_pnts! — Methodset_fdbd_pnts!(value::GenericDER, val) -> Any
Set GenericDER fdbd_pnts.
PowerSystems.set_fe_lim! — Methodset_fe_lim!(value::GenericDER, val) -> Any
Set GenericDER fe_lim.
PowerSystems.set_kWh_Cap! — Methodset_kWh_Cap!(value::GenericDER, val) -> Any
Set GenericDER kWh_Cap.
PowerSystems.set_rrpwr! — Methodset_rrpwr!(value::GenericDER, val) -> Any
Set GenericDER rrpwr.
PowerSystems.set_tF_delay! — Methodset_tF_delay!(value::GenericDER, val) -> Any
Set GenericDER tF_delay.
PowerSystems.set_tV_delay! — Methodset_tV_delay!(value::GenericDER, val) -> Any
Set GenericDER tV_delay.